 Paralleling Relays
WILMARTM Protective Relays - WSYN Series
TERMINAL STRIPS #6 - 32 SCREWS
Function: 25
* ANSI/IEEE C37.90-1978
* UL file No. E58048 * CSA file No. LR61158
Operation:
A. The output relay will energize when all three of the following conditions are met: 1. Voltage differential is below the preset value. 2. Phase angle is below the preset value. 3. Frequency differential is below the preset value. B. The relay is also provided with a "Double Dead Bus" feature: When the voltage on either one of the sensing inputs is below 15-25% of nominal, (Dead Bus Condition), the output relay will energize to permit paralleling.
12 4/ 2 15 / 3 5
4 3/16
3 1/2
7 / 16 4 1 /4 5 2 23 / 3 5
When both sensing voltage are below 15-25% of nominal, the output relay will not energize.
13/64" DIA. 4 MTG. HOLES
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
PART NUMBER SELECTION
Sample Part No. Type: WSYN - Synchro Check Frequency Hz 50 60 400 WSYN-50-120-12DC-A
PRODUCT SPECIFICATIONS
Part Number
Sensing Voltage ...................................
WSYN Series
Single Phase, see Part Number Selection
Sensing Voltage VAC ( 10%) 120 400 200 416 208 440 220 460 230 480 240 525 380 575 Control Voltage ( 20%) 12DC 120AC 24DC 230AC 48DC 380AC 125DC 460AC Options A = two normal open contacts B = two normally closed contacts H = Contacts rated 3 amp at 125 VDC P = Transient Protection Transient Protection - All voltage relays will withstand momentary voltage surges of twice the nominal rated input voltage (standard).
Control Voltage .................................... See Part Number Selection Voltage Differential Adjust Range ....... 4% to 10% of nominal voltage Phase Angle Adjust Range .................. 4 to 10 electrical degrees Frequency Differential Adjust Range Operating Temperature ........................ 0.2 Hz to 0.5 Hz -20o C to +50 oC
Contact Ratings .................................... 5 amp resistive at 120 VAC or 28Vdc Output Contacts ................................... One set N.O., one set N.C.
Notes: 1. Remove black cover screws to gain access to the adjustment potentiometers. 2. Clockwise rotation increases the trip differential setting. 3. Calibration terminals (11) (12) must be connected together to disable the phase angle detector when setting the frequency difference trip point. Once it is set, the connection must be removed.
38
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)


▲Up To Search▲   

 
Price & Availability of WSYN-50-120-12DC-A

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X